FEATURES
Contact Switching capability
Application: For Electric Control System of Communication Power Supply、Engineering Machine、Electro-motion Forklift、Motor Car、Train、Watercraft and UPS etc.
01 Nomination(nomogram)
02 Use conditions required
|
Parameters |
Product code |
ZJ125Yseries |
||
1 |
Ambient temperature: |
(-40~+60)℃ |
2 |
Relative humidity: |
(Up to 98% at +20℃) |
3 |
Vibration freq .at the fixed position:
|
(10~200)Hz、Acceleration≤3.5g
|
4 |
Shocking |
(60~100)time/minute、Acceleration≤4g
|
5 |
Mounting directions |
Optional |
03 Basic technical data
|
Parameters |
Product code |
|||||||
ZJ125Y series |
|||||||||
1 |
Rated coil volt (VDC) |
12 |
24 |
30 |
48 |
60 |
80 |
120 |
|
2 |
Coil Power dissipation (W) |
8~15 |
|||||||
3 |
Operating volt in cold state at (20±5)℃(V) |
Pick-up |
Not above 70% of rated coil volt |
||||||
Release |
(5~40)% Rated coil volt |
||||||||
4 |
Fluctuating range of power supply volt |
(0.85%~110%) rated volt |
|||||||
5 |
Rated volt of contact circuit (V DC) |
60 VDC |
|||||||
6 |
Rated load current of contact circuit (A) |
125A |
|||||||
7 |
Contact volt drop of contact at 100A: |
≤50mV |
|||||||
8 |
Puncture(volt) strength |
50Hz,1000V AC,1min |
|||||||
9 |
Max. make-break ability of contact |
(Connect four times rated load current, make and break once for )5ms |
|||||||
10 |
Mechanical life |
100,000 Ops |
|||||||
11 |
Working duty |
Continuous |
04 Configurational mounting diagram